Honeywell AlarmNet GSMHS Installation And Setup Manual page 21

High security gsm cellular communicator
Table of Contents

Advertisement

PROMPTS
Zn7 Trigger Type
33
(V+)_
Invert Zn7 Y/N
34
(N)_
Restore Zn7 Y/N
35
(Y)_
Delay Zn7 (secs)
36
(00)_
Review? Y/N
37
ENTRY
OPTIONS
 (V+)
 (V–)
 (EOLR)
[Y], [N]
[Y], [N]
[01-15]
[00] = no delay
[Y] = review
[N] = exit
Section 3: Programming the GSMHS
DESCRIPTION
Selects the triggering method for this zone input.
Press the [space] key to scroll through choices.
Inverts the alarm and normal states of the zone 7
trigger; otherwise uses normal input signal.
Enables restore reporting for zone 7.
UL: Must be set to "Y."
Defines the reporting delay in seconds for zone 7.
UL: Must be set to "00."
Reviewing Programming Mode Entries
To review the programming options (to ensure that the
correct entries have been made), press [Y]. The
programming prompts are displayed again. Use the
up/down arrow keys to scroll through the program
fields without changing any of the values. If a value
requires change, simply type in the correct value.
When the last field is displayed, the "REVIEW?"
prompt again appears.
To exit the programming mode, press [N] in
response to the "REVIEW?" prompt, and refer to
Exiting Programming Mode paragraph at the end of
this section.