Honeywell AlarmNet GSMHS Installation And Setup Manual page 26

High security gsm cellular communicator
Table of Contents

Advertisement

GSMHS Installation and Setup Guide
PROMPTS
18
GSM Flt Time
(1 min)_
Flt Rel ON Y/N
19
(N)_
Pwr Loss Rpt Y/N
20
(Y)_
Low Bat Rpt Y/N
21
(Y)_
Tamper Rpt Y/N
22
(Y)_
Lynx Panic Y/N
23
(Y)_
If desired, 4204 mode supports two optional hardwire zone input triggers by making connections to the module's
zone 6 and/or zone 7 terminals and programming the appropriate zone trigger options below.
NOTE: These triggers are not available when using 2-4204 mode.
Zone Trigger Mode provides six hardwire zone input triggers by making connections to the module's zone
terminals and programming the appropriate zone trigger options below. Zones are numbered 1-7, with zone 2
serving as a reporting zone only (see Bell Output Zone below).
Bell Output Zone 1 (and 2): The zone 1 terminal can detect both pulsed and steady signals. If connecting the bell
output to the GSMHS zone causes a bell fault on the control panel, enable the "Trip Inputs 1or2" option. The
GSMHS reports an alarm on zone 1 (fire) when it detects a pulsed signal and an alarm on zone 2 (burglary) when it
detects a steady signal.
Telco Zone and Open/Close Zone: Dedicated zones can be assigned as the Telco fault zone and/or an open/close
(arm/disarm) reporting zone. When triggered, these zones report a Telco line fault or open/close report respectively,
in ADEMCO High-Speed format. Connect the appropriate trigger from the control to the selected zone input for
each of these options.
3-12
4204/
ZONE
ENTRY
2-4204
TRIG.
Important Information Regarding Zone Input Options
OPTIONS
In the event the module detects a communica-
[01-99]
tion path failure, enter the time delay (in
[00] = not
minutes) before the module notifies the control
used
panel with a trouble message (and trips the
Fault Output if used (terminal 11); see next
question). The control panel can then notify
the central station.
UL: Must be one (01) minute.
If enabled, the fault open collector output is
[Y], [N]
normally energized to ground, and de-energizes
(open circuit) in the event of a module fault.
For conditions that trip the fault relay refer to
Module Supervision Features in Section 1.
Set to [Y] if fail-safe mode is desired.
See Wiring for Module Fault Relay in
Section 2.
UL: Must be set to "Y".
Sends a primary power loss report to the
[Y], [N]
central station within 1-3 hours after its
detection. A restore report is sent within 1-3
hours after power is restored.
UL: Must be set to "Y".
[Y], [N]
Sends a low-battery report when a low battery
condition exists. A low-battery restore is
automatically sent when the low battery
condition clears.
Alternate Installations (powered from the
control panel): Must be set to "N."
UL: Must be set to "Y".
[Y], [N]
Sends a tamper report when the module
detects a tamper condition. A tamper restore
is automatically sent when the tamper
condition clears.
UL: Must be set to "Y."
[Y], [N]
Applies only if used with a Lynx, LynxR or
LynxR-EN control LRR trigger connected to
the module's zone terminal.
Reports a Panic alarm on zone 3 when the
module detects a single pulse on zone 1.
No restores are generated for a Panic alarm.
DESCRIPTION

Advertisement

Table of Contents
loading

Table of Contents