Honeywell AlarmNet GSMHS Installation And Setup Manual page 20

High security gsm cellular communicator
Table of Contents

Advertisement

GSMHS Installation and Setup Guide
PROMPTS
Flt Rel ON Y/N
23
(N)_
24
Pwr Loss Rpt Y/N
(Y)_
Low Bat Rpt Y/N
25
(Y)_
Tamper Rpt Y/N
26
(Y)_
ECP mode supports two optional hardwire zone input triggers by making connections to the module's zone 6 and/or
zone 7 terminals and programming the appropriate zone trigger options below.
Each zone input can be programmed to cause an alarm under one of the following conditions:
 (V+), where a positive voltage causes an alarm for normally low connections (voltage trigger, NO, NC)
 (V–), where a ground trigger causes an alarm for normally high connections (open collector, NO, NC)
 (EOLR) End of Line Resistor, where the input is supervised by a 2K EOL resistor. The zone can be triggered
by open collector, voltage trigger, NO, NC.
In addition to the above, zones can be programmed for an Inverted Trigger, where the alarm and
UL
normal states of the zones are inverted; this can serve a fail-safe supervisory purpose for certain
installations.
These zone inputs can also be programmed for restore reporting, and for delayed reporting, which allows time for
the user to abort false alarms.
NOTE: Optional hardwire zones report in ADEMCO High-Speed format.
Enable Zn6 Y/N
27
(N)_
28
Zn6 Trigger Type
(V+)_
29
Invert Zn6 Y/N
(N)_
Restore Zn6 Y/N
30
(Y)_
Delay Zn6 (secs)
31
(00)_
Enable Zn7 Y/N
32
(N)_
3-6
ENTRY
OPTIONS
[Y], [N]
[Y], [N]
[Y], [N]
[Y], [N]
Important Information Regarding Zone Input Options
[Y], [N]
 (V+)
 (V–)
 (EOLR)
[Y], [N]
[Y], [N]
[01-15]
[00] = no delay
[Y], [N]
DESCRIPTION
If enabled, the fault open collector output is normally
energized to ground, and de-energizes (open circuit) in
the event of a module fault. For conditions that trip the
fault relay refer to Module Supervision Features in
Section 1.
Set to [Y] if fail-safe mode is desired.
See Wiring for Module Fault Relay in Section 2.
UL: Must be set to "Y."
Sends a primary power loss report to the central
station within 1-3 hours after its detection. A restore
report is sent within 1-3 hours after power is restored.
UL: Must be set to "Y."
Sends a low-battery report when a low battery
condition exists.
UL: Must be set to "Y."
Sends a tamper report when the module detects a
tamper condition. A tamper restore is automatically
sent when the tamper condition clears.
UL: Must be set to "Y."
Enables alarm reporting for zone 6.
If [N], skip to Prompt 32: "Enable Zn7."
Selects the triggering method for this zone input.
Press the [space] key to scroll through choices.
Inverts the alarm and normal states of the zone 6
trigger; otherwise uses normal input signal.
Enables restore reporting for zone 6.
UL: Must be set to "Y."
Defines the reporting delay in seconds for zone 6.
UL: Must be set to "00."
Enables alarm reporting for zone 7.
If [N], skip to Prompt 37: "Review."