Setting area of operation parameters

The following table describes the setting area of D/A conversion module's operation
parameters.
Address
(Dec.)
0
Specify channel to use
Specify output voltage range
1
Specify output current range
2
Specify input data type
3
Specify CH0 output type
4
Specify CH1 output type
5
Specify CH2 output type
6
Specify CH3 output type
7
-
8
-
9
-
10
-
11
CH0 setting error
12
CH1 setting error
R200
Isolated Analog Output Module 2MLF-DV4S, 2MLF-DC4S User's Guide
September 2010
Description
Honeywell
5. Internal Memory Configuration
5.1. Configuring internal memory
Details
Bit On (1): Channel
used
Bit Off (0): Channel
unused
Bit (00): 1~5V, Bit
(01) : 0~5V
Bit (10): 0~10V, Bit
(11) : -10~10V
Bit (00): 4~20mA
Bit (01): 0~20mA
Bit (00): 0~16000,
Bit (01): -8000~8000,
Bit (10): 0~5000, Bit
(11): 0~10000
"0": outputs the
previous value
"1": outputs the min.
value of output range
"2": outputs the mid.
value of output range
"3": outputs the max.
value of output range
Error code area
Remarks
Read/Write
available
Read
available