Honeywell 2MLF-DV4S User Manual page 24

Isolated analog output module
Table of Contents

Advertisement

2. Specifications
2.1. Performance specifications
Item
Maximum
resolution
Accuracy
Maximum
conversion
speed
Absolute
maximum
output
Number of
output channels
Isolation
method
Terminal
connected
I/O points
occupied
Current
24
Isolated Analog Output Module 2MLF-DV4S, 2MLF-DC4S User's Guide
2MLF-DV4S (Isolated
Voltage Output Type)
Signed value
-8000 ~ 8000
Precise value
4000 ~ 20000
Percentile value
0 ~ 10000
1/16000 (for respective output range)
1~5V
0.250mV
0~5V
0.3125mV
0~10V
0.625mV
±10V
1.250mV
Standard accuracy: ±0.1% or less (when ambient temperature is
25°)
Temperature coefficient: ±80ppm/℃ (0.008 %/℃)
10ms/4 channels
±15V
4 channels/1 module
Photo-coupler isolation between input terminal and PLC power
(Isolation between channels)
18-point terminal
Changeable type: 16 points
Fixed type: 64 points
Internal
DC5V : 200mA
Honeywell
Specification
2MLF-DC4S (Isolated Current
Output Type)
0 ~ 20000
4~20mA
0~20mA
±30mA
Internal
1.0µA
1.25µA
DC5V : 200mA
200
September 2010