Accuracy - Honeywell 2MLF-DV4S User Manual

Isolated analog output module
Table of Contents

Advertisement

2. Specifications
2.3. Characteristics of I/O conversion
2.
If the range is 0~20mA
Digital
Input
-
0
Unsigned
0
0
value
Signed
0
-8000
value
Precise
0
0
value
Percentile
0
0
value
In the case of 0~20mA current output, analog current output for digital value of "1" is
equivalent to 1.25µA.

Accuracy

Although the output range is changed, the accuracy of the analog output does not change.
The following figure shows the accuracy change range at the ambient temperature of 25
± 5°. The analog output range is set between 4 and 20mA and select an unsigned integer
for the input type.
(±0.1% at 25 ± 5°, 80ppm/° at 0 ~ 55°)
32
Isolated Analog Output Module 2MLF-DV4S, 2MLF-DC4S User's Guide
Analog Current Output
5
10
15
4000
8000
12000
-4000
0
4000
5000
10000
15000
2500
5000
7500
Honeywell
Maximum
Resolution
20
20.24
16000
16191
1.25µA
8000
8191
20000
20192
1.0µA
10000
10119
2.0µA
September 2010