Honeywell THX9321 Prestige 2.0 Product Data page 56

Hide thumbs Also See for THX9321 Prestige 2.0:
Table of Contents

Advertisement

®
THX9321 PRESTIGE
2.0 AND THX9421 PRESTIGE
ISU
Installer Setup
Number
Name
8100
Clean Tank / Water
Filter Replacement
Reminder
8100
Humidifier Pad
Replacement
Reminder
9000
Dehumidification
Equipment
9010
Which Sensor will
be used for
Dehumidification
Control?
9020
Which Indoor
Humidity Sensor
should be
displayed on the
Home Screen?
68-0311—02
Table 4. Installer Setup (ISU) Table. (Continued)
Settings
Off
60 Run Time Days
90 Run Time Days
6 Calendar Months
12 Calendar Months
Off
60 Run Time Days
90 Run Time Days
6 Calendar Months
12 Calendar Months
Residential:
None
A/C with Low Speed Fan
A/C with High Speed Fan
Whole House Dehumidifier
Commercial:
None
A/C with Low Speed Fan
A/C with High Speed Fan
Hot Gas Bypass
Dehumidifier
Thermostat (Internal)
Sensor Name (Remote)
Sensor Name (Remote)
Sensor Name (Remote)
Sensor Name (Remote)
Sensor Name (Remote)
Sensor Name (Remote)
(Up to 6 Remote Sensors)
Humidification Sensor
Dehumidification Sensor
®
IAQ WITH EIM
Residential,
Commercial
Default
or Both
Off
Both
Off
Both
None
Both
Thermostat
Both
(Internal)
Humidification
Both
Sensor
56
Requires
EIM
Notes
No
This ISU is only displayed if ISU 8000
Humidifier Type is Steam.
Run Time Days are not shown if ISU 8000
Humidifier Type is set to None.
No
This ISU is only displayed if ISU 8000
Humidifier Type is Bypass or Fan Powered.
Run Time Days are not shown if ISU 8000
Humidifier Type is set to None.
No
See "Dehumidification - Residential"
beginning on page 105 or
"Dehumidification - Commercial"
beginning on page 109.
No
Select a sensor to control dehumidification
(thermostat or an optional remote sensor).
If multiple sensors are installed, you can
use a different sensor for humidification
control. See "Dehumidification control"
beginning on page 130.
Note: Humidity sensing cannot be
averaged.
No
This ISU is only displayed when separate
humidity sensors are used to control
humidification and dehumidification. Only
one of the sensors can be displayed on the
home screen. Select either the
Humidification Sensor or the
Dehumidification Sensor.