Honeywell THX9321 Prestige 2.0 Product Data page 36

Hide thumbs Also See for THX9321 Prestige 2.0:
Table of Contents

Advertisement

®
THX9321 PRESTIGE
2.0 AND THX9421 PRESTIGE
ISU
Installer Setup
Number
Name
3130
Radiant Heat
Cycles Per Hour -
Stage 2
3140
Cool / Compressor
Cycles Per Hour -
Stage 1
Note: "Stage 1" is
not displayed if
there is only 1
stage.
3140
Cool / Compressor
Cycles Per Hour -
Stage 2
68-0311—02
Table 4. Installer Setup (ISU) Table. (Continued)
Settings
1 to 12 CPH
1 to 6 CPH
1 to 6 CPH
®
IAQ WITH EIM
Residential,
Commercial
Default
or Both
3
Both
3
Both
3
Both
36
Requires
EIM
Notes
No
ISU 3010 Temperature Control Options
must be set to Advanced to view or adjust
cycle rate.
This ISU is only displayed when ISU 2010
Heating Equipment Type is Geothermal
Radiant Heat.
The thermostat automatically defaults to
the recommended setting for Geothermal
Radiant Heat (3 CPH).
Cycle rate limits the maximum number of
times the system can cycle in a 1 hour
period measured at a 50% load. For
example, when set to 3 CPH, at a 50% load,
the most the system will cycle is 3 times
per hour (10 minutes on, 10 minutes off).
The system cycles less often when load
conditions are less than or greater than a
50% load.
No
ISU 3010 Temperature Control Options
must be set to Advanced to view or adjust
cycle rate.
This ISU is only displayed when ISU 2070
Cool / Compressor Stages is set to 1 stage.
Cycle rate limits the maximum number of
times the system can cycle in a 1 hour
period measured at a 50% load. For
example, when set to 3 CPH, at a 50% load,
the most the system will cycle is 3 times
per hour (10 minutes on, 10 minutes off).
The system cycles less often when load
conditions are less than or greater than a
50% load.
No
ISU 3010 Temperature Control Options
must be set to Advanced to view or adjust
cycle rate.
This ISU is only displayed when ISU 2070
Cool / Compressor Stages is set to 2
stages.
Cycle rate limits the maximum number of
times the system can cycle in a 1 hour
period measured at a 50% load. For
example, when set to 3 CPH, at a 50% load,
the most the system will cycle is 3 times
per hour (10 minutes on, 10 minutes off).
The system cycles less often when load
conditions are less than or greater than a
50% load.