Honeywell THX9321 Prestige 2.0 Product Data page 37

Hide thumbs Also See for THX9321 Prestige 2.0:
Table of Contents

Advertisement

ISU
Installer Setup
Number
Name
3140
Cool Cycles Per
Hour - Stage 3
3140
Cool Cycles Per
Hour - Stage 4
Table 4. Installer Setup (ISU) Table. (Continued)
Settings
1 to 6 CPH
1 to 6 CPH
®
THX9321 PRESTIGE
2.0 AND THX9421 PRESTIGE
Residential,
Commercial
Default
or Both
3
Commercial
3
Commercial
37
Requires
EIM
Notes
No
ISU 3010 Temperature Control Options
must be set to Advanced to view or adjust
cycle rate.
This ISU is only displayed when ISU 1010
Application is set to Commercial and ISU
2070 Cool Stages is set to 3 stages.
Cycle rate limits the maximum number of
times the system can cycle in a 1 hour
period measured at a 50% load. For
example, when set to 3 CPH, at a 50% load,
the most the system will cycle is 3 times
per hour (10 minutes on, 10 minutes off).
The system cycles less often when load
conditions are less than or greater than a
50% load.
No
ISU 3010 Temperature Control Options
must be set to Advanced to view or adjust
cycle rate.
This ISU is only displayed when ISU 1010
Application is set to Commercial and ISU
2070 Cool Stages is set to 4 stages.
Cycle rate limits the maximum number of
times the system can cycle in a 1 hour
period measured at a 50% load. For
example, when set to 3 CPH, at a 50% load,
the most the system will cycle is 3 times
per hour (10 minutes on, 10 minutes off).
The system cycles less often when load
conditions are less than or greater than a
50% load.
®
IAQ WITH EIM
68-0311—02