Honeywell THX9321 Prestige 2.0 Product Data page 33

Hide thumbs Also See for THX9321 Prestige 2.0:
Table of Contents

Advertisement

ISU
Installer Setup
Number
Name
3050
Staging Control -
Heat Differential
Stage 3
Note: Depending
on the application,
the text displayed
on the screen may
show the specific
heating equipment
type
3060
Staging Control -
Compressor Heat
Differential Stage 1
3060
Staging Control -
Compressor Heat
Differential Stage 2
Table 4. Installer Setup (ISU) Table. (Continued)
Settings
Comfort
1.0° F to 4.0° F from setpoint (in
0.5° F increments)
Comfort
1.0° F to 4.0° F from setpoint (in
0.5° F increments)
Comfort
1.0° F to 4.5° F from setpoint (in
0.5° F increments)
®
THX9321 PRESTIGE
2.0 AND THX9421 PRESTIGE
Residential,
Commercial
Default
or Both
Comfort
Both
Comfort
Both
Comfort
Both
33
Requires
EIM
Notes
No
ISU 3010 Temperature Control Options
must be set to Advanced to view or adjust
this ISU.
This ISU is only displayed for conventional
systems that have 3 heat stages.
The indoor temperature must drop to the
selected differential setting before the
thermostat will turn on the stage of
heating. For example, if stage 3 is set to 2°
F (1.0° C), the indoor temperature must be
2° F (1.0° C) away from the setpoint before
stage 3 turns on. When set to Comfort, the
thermostat will use the stage of heating as
needed to keep the indoor temperature
within 1° F (0.5° C) degree of the setpoint.
No
ISU 3010 Temperature Control Options
must be set to Advanced to view or adjust
this ISU.
This ISU is only displayed if ISU 2010
Heating Equipment Type is Geothermal
Radiant Heat and ISU 2050 Geothermal
Forced Air System is set to Used for
Heating and Cooling.
The indoor temperature must drop to the
selected differential setting before the
thermostat will turn on the stage of
heating. For example, if stage 1 is set to 2°
F (1.0° C), the indoor temperature must be
2° F (1.0° C) away from the setpoint before
stage 1 turns on. When set to Comfort, the
thermostat will use the stage of heating as
needed to keep the indoor temperature
within 1° F (0.5° C) degree of the setpoint.
No
ISU 3010 Temperature Control Options
must be set to Advanced to view or adjust
this ISU.
This ISU is only displayed if ISU 2010
Heating Equipment Type is Air to Air Heat
Pump, Geothermal Heat Pump or
Geothermal Radiant Heat and there are 2
compressor stages.
The indoor temperature must drop to the
selected differential setting before the
thermostat will turn on the stage of
heating. For example, if stage 2 is set to 2°
F (1.0° C), the indoor temperature must be
2° F (1.0° C) away from the setpoint before
stage 2 turns on. When set to Comfort, the
thermostat will use the stage of heating as
needed to keep the indoor temperature
within 1° F (0.5° C) degree of the setpoint.
®
IAQ WITH EIM
68-0311—02

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Thx9421 prestige iaq with eim

Table of Contents