Honeywell THX9321 Prestige 2.0 Product Data page 152

Hide thumbs Also See for THX9321 Prestige 2.0:
Table of Contents

Advertisement

®
THX9321 PRESTIGE
2.0 AND THX9421 PRESTIGE
Typical wiring of a W7213/W7214 Economizer Module for a heat pump system, using a Prestige THX9321 thermostat or
Equipment Interface Module.
Fig. 348. Wiring a W7213/W7214 Economizer Module for a heat pump system.
Typical wiring of a W7212 Economizer Module for a conventional heating system, using a Prestige THX9321 thermostat or
Equipment Interface Module.
Fig. 349. Wiring a W7212 Economizer Module for a conventional heating system.
1 "A" or "L/A" terminal must be configured for Economizer in the installer setup (ISU 2220). These terminals are powered by the
cooling transformer (Rc terminal).
2 Terminal AUX 2 is present only on the Equipment Interface Module.
3 Add a normally closed relay as shown to make the W7213/W7214 Economizer Module compatible with the thermostat. The ther-
mostat energizes the "A" or "L/A" terminal during Occupied Periods.
68-0311—02
®
W7213/W7214 Economizer Module
(See wiring guidelines provided with the product)
O OR B
N
3
4
1
2 & 5
TR1
TR
Transformer
W7212 Economizer Module
(See wiring guidelines provided with the product)
N
3
4
1
2 & 5
TR1
TR
Transformer
IAQ WITH EIM
O/B
1
3
3
O/B
L/A
1
R
120
24
C
VAC
VAC
A
1
R
120
24
VAC
C
VAC
152
Rooftop Unit
Y1
Y2
AUX AUX 2
G
Y
Y2
AUX AUX 2
G
2
Thermostat/EIM
MCR34809
Rooftop Unit
Y1
Y2
W1
W2
G
Y
Y2
W
W2
G
Thermostat/EIM
MCR34257A