Honeywell THX9321 Prestige 2.0 Product Data page 41

Hide thumbs Also See for THX9321 Prestige 2.0:
Table of Contents

Advertisement

ISU
Installer Setup
Number
Name
3200
Heating Throttling
Range
3210
Heating Integral
3220
Heating Derivative
3240
Minimum
Compressor Off
Time
3260
Extended Fan Run
Time in Cool
3260
Extended Fan Run
Time in Heat
4000
Number Of
Schedule Periods
4010
Pre-Occupancy
Purge Duration
Table 4. Installer Setup (ISU) Table. (Continued)
Settings
1° F to 30° F
0, 100 to 25,000 sec
0, 100 to 25,000 sec
Off
1 - 5 minutes
0, 30, 60, 90 seconds, 2, 3, 4, 5,
6, 7, 8, 9, 10, 11, 12, 13, 14, 15
minutes
0, 30, 60, 90 seconds, 2, 3, 4, 5,
6, 7, 8, 9, 10, 11, 12, 13, 14, 15
minutes
2 or 4 periods per day
Off
1 hour
2 hour
3 hour
®
THX9321 PRESTIGE
2.0 AND THX9421 PRESTIGE
Residential,
Commercial
Default
or Both
2° F
Commercial
10,000 sec
Commercial
0 sec
Commercial
5 minutes
Both
0 seconds
Both
0 seconds
Both
4 periods per
Both
day
Off
Commercial
41
Requires
EIM
Notes
No
The default Heating Throttling Range is 2° F
(1.5° C) which is appropriate for most
applications. Do not change this setting
unless advised to do so by Honeywell
technical support.
The throttling range controls the cycling of
the system and helps to compensate for
load changes, equipment sizing and
thermostat mounting location.
No
The default Heating Integral is 10,000
seconds which is appropriate for most
applications. Do not change this setting
unless advised to do so by Honeywell
technical support.
The integral controls how much droop is
used.
No
The default Heating Derivative is 0 seconds
which is appropriate for most applications.
Do not change this setting unless advised
to do so by Honeywell technical support.
The derivative makes adjustments to the
algorithm for fast acting systems.
No
The thermostat has a built in compressor
protection (minimum off timer) that
prevents the compressor from restarting
too early after a shutdown. The minimum-
off timer is activated after the compressor
turns off.
If there is a call during the minimum-off
timer, the thermostat shows "waiting for
equipment" in the display.
No
After the call for cooling ends, the
thermostat keeps the fan on for the
selected amount of time for increased
efficiency. This may re-introduce humidity
into the living space.
No
After the call for heating ends, the
thermostat keeps the fan on for the
selected amount of time for increased
efficiency.
No
Residential:
4 Periods = Wake, Leave, Return, Sleep
2 Periods = Wake, Sleep
Commercial:
4 Periods = Occupied 1, Unoccupied 1,
Occupied 2, Unoccupied 2
2 Periods = Occupied 1, Unoccupied 1
No
Runs the fan 1 to 3 hours before each
occupied period to provide a comfortable
workplace upon arrival.
®
IAQ WITH EIM
68-0311—02