ISU
Installer Setup
Number
Name
4070
Outdoor
Temperature used
with Minimum Cool
Recovery Ramp
Rate
4080
Maximum Cool
Recovery Ramp
Rate
Table 4. Installer Setup (ISU) Table. (Continued)
Settings
Off
-20° F to 100° F
Off
1° F/hr to 20° F/hr
®
THX9321 PRESTIGE
2.0 AND THX9421 PRESTIGE
Residential,
Commercial
Default
or Both
90° F
Commercial
6° F/hr
Commercial
45
Requires
EIM
Notes
No
Off: The cooling system will begin recovery
at the time that is scheduled.
When a Minimum Recovery Ramp Rate is
set, the thermostat will begin recovery
early to ensure the temperature is reached
at the scheduled time.
Set a Minimum Recovery Ramp Rate
based on the rate that the cooling system
can recover at for a hot day in your region.
Default setting is 3° F / hour.
If an outdoor sensor is installed, set an
Outdoor Temperature that is representative
of a hot day in your region to be associated
with the Minimum Recovery Ramp Rate.
The thermostat will begin recovery at the
optimal time based on a calculated ramp
rate, allowing the system to recover on
time and save energy during changing
outdoor conditions.
During recovery, the setpoint changes at a
rate in degrees per hour depending on the
outdoor temperature. If there is no outdoor
sensor, the Minimum Recovery Ramp
Rate is used.
No
Off: The cooling system will begin recovery
at the time that is scheduled.
When a Maximum Recovery Ramp Rate is
set, the thermostat will begin recovery
early to ensure the temperature is reached
at the scheduled time.
Set a Maximum Recovery Ramp Rate
based on the rate that the cooling system
can recover at for a mild day in your region.
Default setting is 6° F / hour.
Set an Outdoor Temperature that is
representative of a mild day in your region
to be associated with the Maximum
Recovery Ramp Rate.
The thermostat will begin recovery at the
optimal time based on a calculated ramp
rate, allowing the system to recover on
time and save energy during changing
outdoor conditions.
During recovery, the setpoint changes at a
rate in degrees per hour depending on the
outdoor temperature.
®
IAQ WITH EIM
68-0311—02