Max. ON-State Voltage Drop
@ Rated Current:
Repetitive Peak OFF-state
Voltage, Vdrm:
DC Analog
Resolution:
Update Rate:
Ranges:
(Changes between V and mA ranges also require link jumper movement.)
Load Impedance:
Isolation:
Range Selection Method:
OUTPUT 2
General
Types Available:
Relay
Contact Type:
Rating:
Lifetime:
Isolation:
1.5V peak.
600V minimum
Eight bits in 250mS (10 bits in 1 second typical,
>10 bits in >1 second typical).
Every control algorithm execution.
0 - 20mA
4 - 20mA
0 - 10V
0 - 5V
0 - 20mA: 500
maximum
4 - 20mA: 500
maximum
0 - 10V: 500
minimum
0 - 5V: 500
minimum
Isolated from all other inputs and outputs.
Link jumper or DIP switch and front panel
code.
Relay, DC Pulse, AC SSR and DC.
Single pole double throw (SPDT).
2A resistive at 120/240V AC.
>500,000 operations at rated voltage/current.
Inherent.
B-5