Output 2 Type/Output 3 Type - Honeywell DCP 50 Product Manual

Digital controller programmer
Table of Contents

Advertisement

7.6

OUTPUT 2 TYPE/OUTPUT 3 TYPE

The type of output for Output 2 and Output 3 is determined by the Option PCB fitted
in the appropriate position (see Figure 7-1) and, in the case of the DC Output Option
PCB being fitted, the setting of Link Jumpers LJ8 and LJ9 on that Option PCB (see
Figure 7-6 and Table 7-3). There are four types of option PCB which may be used for
Output 2 and Output 3:
1. Relay Output Option PCB (no link jumpers)
2. SSR Drive Output Option PCB (no link jumpers)
3. Solid State Output Option PCB (no link jumpers) - Output 2 only
4. Analog DC Output Option PCB (link jumpers as shown in Figure 7-6)
Figure 7-6
DC Output Option PCB
(Output 2/Output 3)
7-6
Table 7-3
Selection of Output 2 &
Output 3 Type (DC)
DC Output Range
DC (0 - 10V)
DC (0 - 20mA)
DC (0 - 5V)
DC (4 - 20mA)
Link Jumpers Fitted
LJ8
LJ9
LJ8
LJ9