Honeywell DCP 50 Product Manual page 72

Digital controller programmer
Table of Contents

Advertisement

Maximum Input Delay
(OFF-ON):
Minimum Input Delay
(ON-OFF):
OUTPUT 1
General
Types Available:
Relay
Contact Type:
Rating:
Lifetime:
Isolation:
DC Pulse/TTL
Drive Capability:
Isolation:
AC SSR
Operating Voltage Range:
Current Rating:
Max. Non-repetitive Surge
Current (16.6ms):
Min. OFF-State
dv
dt
Voltage:
Max. OFF-State leakage @
Rated Voltage:
B-4
1 second
1 second
Relay (as standard), DC Pulse, AC SSR and DC
as options.
Single pole double throw (SPDT).
2A resistive at 120/240V AC.
>500,000 operations at rated voltage/current.
Inherent.
SSR >4.2V DC into 1k
Not isolated from input or other SSR outputs.
20 - 280Vrms (47 - 63Hz)
0.01 - 1A (full cycle rms on-state @ 25°C);
derates linearly above 40°C to 0.5A @ 80°C.
25A peak
@ Rated
500V/µs
1mA rms
minimum.