Terminal Modules; Terminal Module Tm15 - Siemens SINAMICS S120 Commissioning Manual

With startdrive
Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

Diagnostics
6.1 Diagnostics using LEDs
6.1.4

Terminal Modules

6.1.4.1

Terminal Module TM15

Table 6-34
Meanings of the LEDs on the Terminal Module TM15
LED
Color
READY
-
Green
Orange
Red
Green/re
d
Green/
orange
or
Red/
orange
The parameters for activating component recognition using LEDs can be taken from the following reference:
1)
Reference: SINAMICS S120/S150 List Manual
306
Status
Off
The electronics power supply is missing or outside the permis‐
sible tolerance range.
Continuous
The component is ready for operation. Cyclic DRIVE-CLiQ com‐
light
munication is taking place.
Continuous
DRIVE-CLiQ communication is being established.
light
Continuous
This component has at least one fault.
light
Note:
The LED is activated irrespective of whether the corresponding
messages have been reconfigured.
Flashing
Firmware is being downloaded.
light 0.5 Hz
Flashing
Firmware download is complete. The system waits for POWER
light 2 Hz
ON.
Flashing
Component recognition via LED is activated
light
Note:
Both options depend on the LED status when component rec‐
ognition is activated.
Description, cause
1)
.
Commissioning Manual, 06/2020, 6SL3097-5AA10-0BP2
Remedy
Correct and ac‐
knowledge the fault.
Carry out a POWER
ON.
Commissioning with Startdrive

Advertisement

Table of Contents
loading

Table of Contents