Overview
Upon delivery, the PROFINET interface X150 of the drive does not have an assigned IP address.
If a cyclic connection already exists from SINAMICS to the controller, it is no longer possible to
assign an IP address.
The following data is automatically assigned to the X150 PROFINET interface in the project:
• IP address: 192.168.0.1
• Subnet mask: 255.255.255.0
The IP address and subnet mask are located in the subnet of an S71500 controller, which
simplifies the linking of the control system and drive.
Requirements
• An online connection to the drive exists, and you have made a search for the drives under
"Online access" in the appropriate interface with "Update accessible devices".
• The device is displayed.
Procedure
To assign an IP address to the PROFINET interface of your drive, proceed as follows:
1. Double-click "Online & Diagnostics" under "Online access" in the project tree.
2. Double-click the "Functions" entry in the secondary navigation of the working area.
3. Double-click the "Assign IP address" entry.
4. Enter an IP address that matches your project.
5. Enter an appropriate subnet mask.
6. Click on "Assign IP address"
7. Update the display under "Online access"
The assigned IP address is displayed. The MAC address is read out automatically.
Result
The IP address has been assigned to the drive.
Commissioning with Startdrive
Commissioning Manual, 06/2020, 6SL3097-5AA10-0BP2