6.1.2.4

Smart Line Modules booksize 5 kW and 10 kW

Table 6-10
Meaning of the LEDs at the Smart Line Modules 5 kW and 10 kW
LED
Color
READY
Green
Yellow
Red
DC LINK
Yellow
Red
6.1.2.5

Smart Line Modules booksize 16 kW to 55 kW

Table 6-11
Meaning of the LEDs at the Smart Line Modules ≥ 16 kW
State
Ready
DC link
Off
Off
Green
Off
Orange
Red
Orange
Orange
Red
Green / red
flashing light
0.5 Hz
Commissioning with Startdrive
Commissioning Manual, 06/2020, 6SL3097-5AA10-0BP2
State
Description, cause
Off
Electronic power supply is missing or outside permissible
tolerance range.
Continu‐
Component is ready to operate.
ous light
Continu‐
Pre-charging not completed.
ous light
Bypass relay dropped out
EP terminals not supplied with 24 VDC.
Continu‐
Overtemperature
ous light
Overcurrent
Off
Electronic power supply is missing or outside permissible
tolerance range.
Continu‐
DC link voltage within permissible tolerance range.
ous light
Continu‐
DC link voltage outside permissible tolerance range.
ous light
Line supply fault.
Description, cause
Electronic power supply is missing or outside permissible tol‐
erance range.
The component is ready for operation and cyclic DRIVE-CLiQ
communication is taking place.
The component is ready for operation and cyclic DRIVE-CLiQ
communication is taking place.
The DC link voltage is present.
The component is ready for operation and cyclic DRIVE-CLiQ
communication is taking place.
The DC link voltage is too high.
DRIVE-CLiQ communication is being established.
At least one fault is present in this component.
Note:
LED is controlled irrespective of the corresponding messages
being reconfigured.
Firmware is being downloaded.
Diagnostics
6.1 Diagnostics using LEDs
Remedy
Diagnose fault (via output
terminals) and acknowl‐
edge it (via input terminal)
Check the line voltage.
Remedy
Check the line voltage
Remedy and acknowledge fault