Routable Binary Input Signals (SPS Data Type)
The next figure shows the possible sources for connecting a binary input signal. Depending on the source,
different quality attributes can be set:
CFC chart: See description in chapter
GOOSE connection: See description in chapter
GOOSE Values
Device hardware: No quality attributes are set and supported.
[loquali2-230212-01.tif, 2, en_US]
Figure 3-31
For this signal type (SPS), you can influence the processing of the quality, see overview in
The following figure shows the possible influence on a binary input signal of a recorder.
In the DIGSI 5 project tree, double-click Information routing.
In the operating range, select the desired binary input signal.
In the Properties window, select the Details entry. There, you will find the item Processing quality
attributes.
SIPROTEC 5, Fault Recorder, Manual
C53000-G5040-C018-5, Edition 11.2017
3.3.3 Quality Processing/Affected by the User in CFC Charts
Sources for Connecting a Binary Input Signal
3.3.2 Quality Processing/Affected by the User for Received
System Functions
3.3 Processing Quality Attributes
Figure
3-30.
79