Function-Group Types
6.4 Function-Group Type Phasor Measurement Unit (PMU)
Name Displayed in the DIGSI Function
Group Connections
Measuring point I-3ph 1[ID 2]
Measuring point I-1ph 1[ID 3]
Measuring point U-1ph 1[ID 4]
Table 6-6
Path Displayed in DIGSI 5
(Can Be Edited)
PMU 1:
Transf.bin.1:
>BinaryInfo.6
PMU 1:
Transf.bin.2:
>BinaryInfo.8
PMU 1:
Transf.bin.10:
>BinaryInfo.3
Data is transmitted continuously from the PMU to the PDC at the configured reporting rate. The transmission is
terminated by a corresponding trip command from the PDC or when the connection between the PDC and the
PMU is interrupted.
Communication between the PMU and the PDC can be passed via TCP or UDP protocols.
The following ports are used for data transmission:
TCP: Port 4712
UDP: Port 4713
The ports must be configured on the PDC.
If you are using the UDP protocol for communication between the PMU and the PDC, you can set either
command mode or asynchronous response mode as the communication mode. In asynchronous
response mode, data can be transmitted continuously to preset PDC destination addresses in IEEE C37.118
format without a PDC having to request transmission of the synchrophasor data via a close command to the
PMU.
Up to 3 different PDCs can be connected to one device PMU at the same time. The IP addresses of the
maximum 3 PDCs are set in the PMU function group. If 4 device PMUs are configured, this enables support for
up to 12 PDCs.

Parameterizing the PMU with DIGSI

6.4.6
You configure and parameterize the Phasor Measurement Unit with DIGSI. After a device has been added in a
DIGSI project, one or more communication modules that support synchrophasors can be configured as PMUs.
The device module supports a maximum of 2 communication modules that can be configured as PMUs. If
more than 2 PMUs are needed, the device must be expanded with a CB202 plug-in module assembly (expan-
sion module), which can accommodate 2 more communication modules.
The following communication modules support synchrophasors:
ETH-BA-2EL (2 x Ethernet electric, RJ45)
ETH-BB-2FO ( 2 x Ethernet optical, 2 km, LC duplex)
158
Possible Binary Information Names
Depending on the Connection Type, Name Transferred to the
PDC (in case it cannot be assigned automatically)
MP-I3ph IA ID02
MP-I3ph IB ID02
MP-I3ph IC ID02
MP-I3ph I1 ID02
MP-I1ph ID03
MP-V1ph ID03
Name Transferred to the PDC
(Cannot be Edited)
BIN-01-INFO-6
BIN-02-INFO-8
BIN-10-INFO-3
SIPROTEC 5, Fault Recorder, Manual