Siemens SIPROTEC 5 Manual page 164

Fault recorder, v7.50 and higher
Hide thumbs Also See for SIPROTEC 5:
Table of Contents

Advertisement

Function-Group Types
6.4 Function-Group Type Phasor Measurement Unit (PMU)
[scaddios-140213-01.tif, 1, en_US]
Figure 6-22
[scroutin-210415, 1, en_US]
Figure 6-23
The maximum numbers of measuring points that can be routed for one PMU are:
2 x 3-phase voltage measuring points
2 x 3-phase current measuring points
2 x 1-phase voltage measuring points
2 x 1-phase current measuring points
You can assign all supported measuring points to any PMU, see the following figure. However, each PMU must
be connected to a 3-phase voltage measuring point.
164
Adding Additional Input/Output Modules
Assignment of the Current and Voltage Inputs of the Added Input/Output Modules on Meas-
uring Points
SIPROTEC 5, Fault Recorder, Manual