Siemens SIPROTEC 5 Manual page 280

Fault recorder, v7.50 and higher
Hide thumbs Also See for SIPROTEC 5:
Table of Contents

Advertisement

Fault Recorder
7.4 Trigger Functions 1-Phase
Parameter Value
on
off
test
Parameter: Max. Trigger Active/Max. Trigger/Max. Trigger Hysteresis
Default setting (_:9781:101) Max. trigger active = yes
Default setting (_:9781:105) Max. trigger = 1.200 A
Default setting (_:9781:113) Max. trigger hysteresis = 0.980 p.u.
With the Max. trigger active parameter, you activate the level trigger in order to monitor the RMS value
of the current and to prevent exceeding the set values..
Parameter Value
yes
no
The hysteresis is preset the factory to 0.980 p.u. of the parameterMax. trigger and can be adjusted.
Parameter: Min. Trigger Active/Min. Trigger/Min. Trigger Hysteresis
Default setting (_:9781:102) Min. trigger active = yes
Default setting (_:9781:106) Min. trigger = 0.800 A
Default setting (_:9781:114) Min. trigger hysteresis = 1.020 p.u.
With the Min. trigger active parameter, you activate the level trigger in order to monitor the RMS value
of the current and to prevent it from dropping below the set values.
Parameter Value
yes
no
The hysteresis is preset at the factory to 1.020 p.u. (equal to 2 %) of the parameter Min. trigger and can
be adjusted.
Parameter: dM/dt Rise Active - dM/dt Rise (/Filter Time) - dM/dt Rise Hysteresis - Filter Time
Default setting (_:9781:103) dM/dt rise active = no
Default setting (_:9781:107) dM/dt rise (/Filter time) = 0.300 A
Default setting (_:9781:115) dM/dt rise hysteresis = 0.980 p.u.
Default setting (_:9781:112) Filter time = 2 periods
With the dM/dt rise active parameter, you activate the gradient trigger in order to monitor the positive
gradients of the RMS value of the current, using the set filtering time (input in periods).
Parameter Value
yes
no
The hysteresis is preset at the factory to 0.980 p.u. (equal to 2 %) of the parameter dM/dt rise (/Filter
time) and can be adjusted.
280
Description
The function block I RMS Trig is activated and the RMS value of the current
is monitored according to the set trigger parameter.
The function block I RMS Trig is deactivated.
The function block I RMS Trig is activated for test purposes.
Description
The RMS value of the current is monitored for overcurrent.
The RMS value of the current is not monitored for overcurrent.
Description
The RMS value of the current is monitored for undercurrent.
The RMS value of the current is not monitored for undercurrent.
Description
The positive gradient of the RMS value of the current is monitored.
The positive gradient of the RMS value of the current is not monitored.
SIPROTEC 5, Fault Recorder, Manual
C53000-G5040-C018-5, Edition 11.2017