7.6.1.3
Routing the Measurands in DIGSI 5 for Processing in SICAM PQS
NOTE
i
i
SICAM PQS allows you, among others, to analyze power quality data. Different routing modules are avail-
able for recorder routing in DIGSI 5. These modules can have different calculation methods and the refresh
rates of the measurands.
If you record the same measurands using different calculation methods and refresh rates, Siemens recom-
mends routing these measurands to different recorders so that SICAM PQS can process these measurands.
EXAMPLE:
The Routing f and PQ 10/12 cyc routing modules record the measurands with different refresh rates.
Route the same measurands having different calculation methods and refresh rates to different recorders. The
following figure shows an example for suitable routing of similar measurands.
[sc pq, 1, en_US]
Figure 7-71
Recorder Routing V
7.6.2
7.6.2.1
Overview of Functions
The Recorder routing V function starts when there is an exceedance of the set frequency and voltage toler-
ance values.
You can find more information on the Recorder routing V function in chapter
Group.
7.6.2.2
Structure of the Function
The Recorder routing V function is preconfigured once at the factory. Within the Voltage 3-phase function
group, the Recorder routing V function can be operated only once.
You can find more information on the Recorder routing V function in the chapters
Function Group
7.6.2.3
Indications
Indications can be routed on recorders that are available via the GOOSE configurator.
Only SPS indications can be routed in DIGSI 5.
SIPROTEC 5, Fault Recorder, Manual
C53000-G5040-C018-5, Edition 11.2017
Example for Routing
and
7.6.1.2 Using Measurands
7.6 Measurands and Recorder Routing Functions
.
Fault Recorder
6.1.2 Structure of the Function
6.1.2 Structure of the