Fault Recorder
7.2 Function-Group Type Recorder
7.2.11.2

Triggering Without the Retrigger Blocking Time

Trigger with Pre-Trigger and Post-Trigger Times
[dwtrig01-140213-01.tif, 1, en_US]
Figure 7-34
a
Trigger rising edge
b
Trigger falling edge
c
End of recording
t
Time line
When a trigger event occurs, the start trigger (a) trips a fault record.
The first part of the recording records the signal profile before the trigger event (Pre-trigger time). After-
wards, the fault (a) to (b) is recorded. To evaluate the signal behavior even after the failure, the further signal
profile up to the end of the post-trigger time (c) is registered.
Trigger with Maximum Record Time
The maximum record time is used for the limit of the fault-record length.
[dwtrig02-140213-01.tif, 1, en_US]
Figure 7-35
a
Trigger rising edge
b
Trigger falling edge
c
End of recording
t
Time line
254
Trigger with Pre-Trigger and Post-Trigger Times
Trigger with Pre-trigger Time and Maximum Recording Time
SIPROTEC 5, Fault Recorder, Manual