Siemens SIPROTEC 5 Manual page 229

Fault recorder, v7.50 and higher
Hide thumbs Also See for SIPROTEC 5:
Table of Contents

Advertisement

are stored and combined into a single file. That is to say, that all 10-minute intervals, 144 files will be replaced
by a single file and all 2-hour intervals, 12 files will be replaced by a single file.
The PQDIF files will be filed according to the following nomenclature:
Subdirectory: Identification of the continuous recorder and the recorder ID: /Cont_PQDif_fffe
ID of the recording (for example, /00000001)
ID of the recorder (for example, fffe)
Date Year/Month/Day: YYYYMMTT (for example, 20130814)
Time of the recording hour/minute/second: hhmmss (for example, 211016)
Example of a PQDIF file path: /Cont_PQDif_fffe/00000001_fffe_20130814_211016.pqd
[leIEC_Browser-270813, 1, en_US]
Figure 7-18
(1)
Recording of the current day
(2)
Recording of the oldest day
(3)
One file per recording day
SIPROTEC 5, Fault Recorder, Manual
C53000-G5040-C018-5, Edition 11.2017
Organization of PQDIF Files
Fault Recorder
7.1 Introduction to DIGSI 5
229