Application And Setting Notes; Settings; Information List - Siemens SIPROTEC 5 Manual

Fault recorder, v7.50 and higher
Hide thumbs Also See for SIPROTEC 5:
Table of Contents

Advertisement

The phase rotation is important for protection functions which process phase, loop, and directional informa-
tion. You can set the phase sequence with the Phase sequence parameter in the function block General of
the power-system data (see chapter
To supervise the phase rotation, the device compares the measured phase sequence with the set phase
sequence. For abnormal phase sequences, the indication
The connection of the voltages to the device does not depend on the selected phase sequence. The connec-
tion diagrams are shown in chapter
Release Condition
The supervision of the voltage phase rotation is carried out when all measured phase-to-phase voltages are
greater than 40 V.
Blocking of the Function
The following blockings reset the function completely:
Via the binary input signal
Via a protection pickup
The pickup signal from a protection function blocks the indication
Delay failure indication
When the device detects an inverted phase-rotation direction for the duration of the Delay failure indi-
cation, the indication
8.3.4.4

Application and Setting Notes

Parameter: Delay failure indication
Recommended setting value (_:6) Delay failure indication = 5.00 s
Set the Delay failure indication parameter so that overfunctions due to disturbing influences (such as
switching operations) are avoided. Siemens recommends using the default setting.
8.3.4.5

Settings

Addr.
Supv. ph.seq.V
_:1
_:6
8.3.4.6

Information List

No.
Supv. ph.seq.V
_:82
_:54
_:52
_:53
_:71
SIPROTEC 5, Fault Recorder, Manual
C53000-G5040-C018-5, Edition 11.2017
5 Power-System
A
Appendix.
>Block function from an external or internal source
Failure is generated.
Parameter
C
Supv. ph.seq.V:Mode
Supv. ph.seq.V:Delay
failure indication
Information
Supv. ph.seq.V:>Block function
Supv. ph.seq.V:Inactive
Supv. ph.seq.V:Behavior
Supv. ph.seq.V:Health
Supv. ph.seq.V:Failure
8.3 Supervision of the Secondary System
Data).
Failure is generated.
Failure .
Setting Options
off
on
test
0.00 s to 100.00 s
Supervision Functions
Default Setting
off
5.00 s
Data Class
Type
(Type)
SPS
I
SPS
O
ENS
O
ENS
O
SPS
O
379