Siemens SIPROTEC 5 Manual page 127

Fault recorder, v7.50 and higher
Hide thumbs Also See for SIPROTEC 5:
Table of Contents

Advertisement

Addr.
Supv. sum I
_:2431:1
_:2431:102
Supv.ADC sum I
_:2401:1
Measuring Point I-1ph
Addr.
General
_:2311:101
_:2311:102
_:2311:103
_:2311:104
_:2311:116
SIPROTEC 5, Fault Recorder, Manual
C53000-G5040-C018-5, Edition 11.2017
Parameter
C
Supv. sum I:Mode
Supv. sum I:Threshold
1 A @ 100 Irated 0.030 A to 10.000 A
5 A @ 100 Irated 0.15 A to 50.00 A
1 A @ 1.6 Irated
5 A @ 1.6 Irated
_:2431:101
_:2431:6
Supv.ADC sum I:Mode
Parameter
C
General:Rated primary
current
General:Rated secondary
current
General:Current range
General:Internal CT type
General:Term. 1,3,5,7 in
dir. of obj.
Setting Options
off
on
test
0.001 A to 1.600 A
0.005 A to 8.000 A
Supv. sum I:Slope factor
Supv. sum I:Delay failure indi-
cation
off
on
test
Setting Options
1.0 A to 100000.0 A
1 A
5 A
1.6 x IR
100 x IR
CT protection
CT measurement
CT Process bus
no
yes
Power-System Data
5.8 Settings
Default Setting
off
0.100 A
0.50 A
0.100 A
0.500 A
0
0
.
.
0
1
0
0
t
o
0
.
9
5
0
5
.
.
0
0
0
0
s
s
t
o
1
0
0
.
0
0
s
off
Default Setting
1000.0 A
1 A
100 x IR
CT protection
yes
127