Application And Setting Notes; Settings; Information List - Siemens SIPROTEC 5 Manual

Fault recorder, v7.50 and higher
Hide thumbs Also See for SIPROTEC 5:
Table of Contents

Advertisement

Supervision Functions
8.3 Supervision of the Secondary System
Delay failure indication
If it falls below the balance factor Threshold min/max and at the same time the maximum phase-to-phase
voltage exceeds the Release threshold, the delay of the failure indication begins, (parameter: Delay
failure indication). If both conditions persist during this time, the indication Failure is generated.
Blocking the Function
The following blockings reset the picked up function completely:
Externally or internally via the binary input signal
A protection pickup
The pickup signal of a protection function blocks the
8.3.2.4

Application and Setting Notes

Parameter: Threshold min/max
Recommended setting value (_:102) Threshold min/max = 0.75
The Threshold min/max parameter is used to set the ratio between the minimum (V
(V
) phase-to-phase voltage. Siemens recommends using the default setting.
max
Parameter: Release threshold
Recommended setting value (_:101) Release threshold = 50 V
With the Release threshold parameter you set the lower limit of the maximum phase-to-phase voltage
(V
). Siemens recommends using the default setting.
max
Parameter: Delay failure indication
Recommended setting value (_:6) Delay failure indication = 5.00 s
Set the Delay failure indication parameter so that overfunctions due to disturbing influences (such as
switching operations) are avoided. Siemens recommends using the default setting.
8.3.2.5

Settings

Addr.
Supv. balan. V
_:1
_:101
_:102
_:6
8.3.2.6

Information List

No.
Supv. balan. V
_:82
_:54
_:52
374
Parameter
C
Supv. balan. V:Mode
Supv. balan. V:Release
threshold
Supv. balan. V:Threshold
min/max
Supv. balan. V:Delay
failure indication
Information
Supv. balan. V:>Block function
Supv. balan. V:Inactive
Supv. balan. V:Behavior
>Block function
Failure indication.
Setting Options
off
on
test
0.300 V to 170.000 V
0.58 to 0.95
0.00 sto 100.00 s
Data Class
(Type)
SPS
SPS
ENS
SIPROTEC 5, Fault Recorder, Manual
C53000-G5040-C018-5, Edition 11.2017
) and the maximum
min
Default Setting
off
50.000 V
0.75
5.00 s
Type
I
O
O