Siemens SIPROTEC 5 Manual page 159

Fault recorder, v7.50 and higher
Hide thumbs Also See for SIPROTEC 5:
Table of Contents

Advertisement

These modules are then freely assignable to ports E, F, N, or P of the device, see
selected port in the (_:10621:104) Port. This parameter is automatically managed by DIGSI and cannot
be changed.
[sccommod-140213-01.tif, 1, en_US]
Figure 6-17
NOTE
i
i
Port M of the CB202 plug-in module assembly is used to accommodate measuring-transducer modules and
cannot be used for the installation of communication modules.
Addressing
You must configure the respective Ethernet address (IP address, subnet mask, etc.) for each communication
module in DIGSI. This is done in the DIGSI General settings properties dialog of the communication module in
item Ethernet addresses and so forms the IP address for the respective PMU.
[scethern-210415, 1, en_US]
Figure 6-18
In the DIGSI properties dialog for channel 1, select the synchrophasor protocol, see the following figure.
SIPROTEC 5, Fault Recorder, Manual
C53000-G5040-C018-5, Edition 11.2017
Placement of Communication Modules
Ethernet Address Configuration
6.4 Function-Group Type Phasor Measurement Unit (PMU)
Figure
Function-Group Types
6-17. You can view the
159