EN - Quick installation and
start-up guide
This guide instructs how to install and start-up the ACS560 drive of all frame sizes
(R0...R8). For complete information, see the drive ACS560 standard control program
firmware manual (3AXD50000044997[English]) and ACS560 drives (0.75 to 160
kW, 1.0 to 215 hp) hardware manual (3AXD50000044998[English]).

General considerations

Obey the safety instructions
WARNING! Obey these instructions. If you ignore them, injury or death, or
damage to the equipment can occur.
If you are not a qualified electrician, do not do electrical installation work.
Do not work on the drive, motor cable or motor when main power is
applied. If the drive is already connected to the input power, wait for 5
minutes after disconnecting the input power.
Do not work on the control cables when power is applied to the drive or
to the external control circuits.
Use the lifting eyes of the drive when you lift the drive. Do not tilt the
drive. The drive is heavy and its center of gravity is high. An overturning
drive can cause physical injury.
Make sure that debris from borings and grindings does not enter the
drive when installing.
Make sure that the floor below the drive and the wall where the drive is
installed are non-flammable.
Reform the capacitors
Reform the capacitors if the drive is stored for a year or more.
The manufacturing date is on the type designation label which is attached to the
drive. The serial number format MYYWWRXXXX represents the month, year and
the week.
YY: 13, 14, 15, ... for 2013, 2014, 2015, ...
WW: 01, 02, 03, ... for week 1, week 2, week 3, ...