Code
Warning/Aux
(hex)
code (aux code
visible only on
assistant con-
trol panel and
drive composer)
A7A2
Mechanical
brake opening
failed
A7C1
FBA A communic-
ation
A7CE
EFB comm loss
A7EE
Panel loss
A88F
Cooling fan
A8A0
AI supervision
0001 – AI1 less minimum
0002 – AI1 greater maximum
A8A1
RO life warning
0001 – Relay output 1
0002 – Relay output 2
Cause
Status of mechanical
brake acknowledgment is
not as expected during
brake open.
Cyclical communication
between drive and field-
bus adapter module A or
between PLC and fieldbus
adapter module A is lost.
Communication lost in
embedded fieldbus (EFB).
Communication lost
between control panel or
PC tools and drive.
Maintenance timer limit
exceeded.
Analog signal is beyond
limits.
The relay has changed
states more than the re-
commended number of
times.
What to do
Check mechanical brake connec-
tion.
Check mechanical brake settings in
parameter group 44 Mechanical
brake control.
Check that acknowledgment signal
matches the actual status of brake.
Check the status of fieldbus com-
munication and cable connections.
Check the status of the fieldbus
master and cable connections to
the EIA-485/X5 terminals 29, 30 and
31 on the control unit.
Check PC tool or control panel con-
nection. Disconnect and reconnect
the control panel.
Replace the drive cooling fan. Para-
meter 05.04 Fan on-time counter
shows the running time of the
cooling fan.
Check the signal level, input wiring,
and the defined limits.
0003 – AI2 less minimum
0004 – AI2 greater maximum
Change the control board or stop
using the relay output.
0003 – Relay output 3