130 Technical data
gR fuses
Drive type
Minimum
ACS560-
short cir-
cuit cur-
rent
3-phase UN = 380...480 V
02A6-4
48
03A3-4
48
04A0-4
80
05A6-4
80
07A2-4
128
EN
09A4-4
128
12A6-4
200
HI
017A-4
256
025A-4
400
033A-4
170
039A-4
170
046A-4
280
062A-4
380
073A-4
480
088A-4
480
106A-4
700
145A-4
1000
169A-4
1280
206A-4
1520
246A-4
2050
293A-4
2200
1) minimum short-circuit current of the device
Input cur-
rent
Rated cur-
rent I N
1)
A
A
4.2
5.3
6.4
9.0
11.5
15.0
20.2
27.2
40.0
32.0
38.0
45.0
62
73
88
106
145
169
206
246
293
gG (IEC 60269)
I 2 t
voltage
A 2 s
A
25
125
25
125
32
275
32
275
40
490
40
490
50
1000
63
1800
80
3600
63
1450
63
1450
80
2550
100
4650
125
8500
160
16000
200
15000
250
28500
315
46500
350
68500
450
105000
500
145000
Rated
ABBdesig-
IEC 60269
nation
type
V
690
170M2694
690
170M2694
690
170M2695
690
170M2695
690
170M2696
690
170M2696
690
170M2697
690
170M2698
690
170M2699
690
170M1565
690
170M1565
690
170M1566
690
170M1567
690
170M1568
690
170M1569
690
170M3815
690
170M3816
690
170M3817
690
170M3818
690
170M5809
690
170M5810
size
00
00
00
00
00
00
00
00
00
000
000
000
000
000
000
1
1
1
1
2
2