Figure 7-34: Low range value verification
3.
Adjust the calibrator to apply the high (100%) value of the signal range.
4.
Wait for the value in Current Value to stabilize
5.
Verify that Current Value displays a value equal or close to the target range high (100%) value
(Figure
7-35).
1 5 0 | R MC-1 00 | 2 10 5 55 2MN A E
(Figure
7-35).