Figure 7-32: Calibration complete
30. Verify that the Entry, Reading, and Target values update, and the Current Value field displays
the calibrated value based on the defined range
from the calibrator is 12 mA. This value represents 750 PSI.
1 4 8 | R MC-1 00 | 2 10 5 55 2MN A E
(Figure
7-33). In this example the input signal