20. Click 100% Cal Point. The Enter 100% Calibration Value box displays
21. Type the range high value into the entry field. (1500.000 in this example).
Figure 7-28: High (100%) Calibration value entry field
22. Adjust the calibrator to apply the high value (100%) of the signal range. For example, if the
signal range of the external device is 4 to 20 mA, apply 20 mA.
23. Observe the value in the Current Reading field
20 mA input is approximately 5 Vdc (0.02 * 250 = 5 Vdc).
(Figure
7-29). The expected voltage value for a
21 05 55 2MN A E | RM C-1 00 | 1 4 5
(Figure
7-28).