Table 6-3: User-enabled services on the RMC

Service
Default
Name
state
SSH/SFTP
Disabled
Service
Totalflow
Enabled
Software
Update
Service
6.2.2

Open Transmission Control Protocol (TCP) ports

The table below lists the open TCP ports on the RMC. These ports are used for all TCP/IP based
connections which are supported by the Ethernet ports.
Protocols over TCP can be standard like SSH, or proprietary like Totalflow (Remote or Local).

Table 6-4: Open TCP ports on the RMC

Default
User-
TCP port
configurable
9999
Yes
65535
No
9696
No
502
Yes
IMPORTANT NOTE: For connections with user-configurable ports, use the default value or assign
a different port number from the range of 1024 to 65534. Connections using non-default TCP ports
are handled by additional Totalflow/TCP communication or Modbus TCP applications configured with
different TCP ports. For example, the figure below shows an additional Totalflow/TCP application
(named ControlGroup) with a different TCP port (10001).
Figure 6-1: Totalflow/TCP application instance with non-default TCP port
1 0 0 | R MC-1 00 | 2 10 5 55 2MN A E
Description
Serves connection requests for
secure login shell and file
transfer. Supports connection
requests from third-party
SSH/SFTP clients
Enables or blocks the ability of
the device loader to update the
embedded software.
Protocol using
Description
the port
Totalflow/TCP
Assigned to connections used for device monitoring,
configuration and data collection or polling. PCCU,
WinCCU, TDS and third-party SCADA systems request
these connections.
Device
Assigned to the device loader connections for device
Loader/TCP
software update.
PCCU requests this type of connection.
SSH/TCP
Assigned to secure shell (SSH/SFTP) connections.
Third-party SSH/SFTP clients request these connections.
Modbus /TCP
Assigned to connections between the RMC and external
Modbus devices for communication and data transfer
Security feature available
Authentication based on private-public key
pairs, passphrase-protected keys
None specific to the service. Must use Bi-
level security passcode or Role-Based
Authentication (Role-Based Authentication,
RBAC)