Advertisement

Figure 7-18: AI 2 set to current mode
6.
Turn on the calibrator.
7.
Click the Calibrate icon on the PCCU toolbar. The Analog Input 1-tab displays a request to take
an application out of HOLD
IMPORTANT NOTE: The calibration mode automatically places active measurement applications
on hold. This is not required for I/O calibration. The calibration navigation tree in
four AGA3 applications. The checkmark indicates that they are all in Hold mode. Pop-ups display to
remove each application from hold. Accept them all. Requests display for each application, one at a
time, until the last application is out of hold.
1 3 8 | R MC-1 00 | 2 10 5 55 2MN A E
(Figure
7-19).
Figure 7-19
shows