Toshiba GR200 Series Instruction Manual page 1110

Hide thumbs Also See for GR200 Series:

Advertisement

10.2.16 Supervision of current in zero-sequence (I0 error)
The zero-phase-sequence current entering to the input circuit is monitored; it is possible to
provide a high sensitivity to detect the failure using the residual circuit current. Equation
(10.2-2) is represented for the supervision:
1.
where,
I e
Max(|I a |, |I b |, |I c |)
k
:
0
†Note: The rated current above the equation is defined with the setting of the VCT. For
more information regarding the VCT, see Chapter
Transformer module for AC analog input
Error level
(i)
Generally, the default error level has been set at level 3 (Minor error), but the user can program
the level using setting [CHK_IZ:LVl].; then, set On for the settings [CHK_IZ:Sw]. The time to
detect can be set using [CHK_IZ:Timer], which is set for 15 seconds as default. If the error is
cleared, resetting will be performed after the elapse of setting time.
Error message
(ii)
When detecting an error, an error message can be shown on the LCD screen and an LED is lit.
Table 10.2-33 Error messages provided by the supervisor in CHK_IZ
Message and level
I0 error
Error level
Table 10.2-34 Detailed information in Hexadecimal in CHK_IZ
Display area
N/A
| I
|
+ I
+ I
− I
a
b
c
e
≥ 0.1 × Max (| I
3
Residual current
The largest amplitude among I a , I b and I c
5% of the rated current†
Meaning of the information
Detection of flowing the zero-sequence current
Minor error (Level 3)
Meaning of the detailed information
(No information is displayed)
- 1089 -
| , | I
| , | I
|) + k
a
b
c
0
Technical description:
.
6F2S1915 (0.46)
(10.2-2)
GRZ200 (Soft 031 & 032)