PWS alarm threshold setting
The IED has power supply module (PWS) at the far left slot. The user can confirm DC rated
voltage on the hardware nameplate by checking the cord at Positions '8', but the user should
select either alarm thresholds for dropping DC voltage by inserting a jumper on the PWS
Section Power supply module
(Figure 13.5-1). See
7
8
- x
1 -
Figure 13.5-1 Alarm threshold set on PWS module
CAUTION
Note: A short-wire is connected between terminal screws No. 35–37 ( No.35–36 for type
using the ring terminal). It is done by the manufacturer. The user shall remove
that when the user undertakes the dielectric voltage test for the IED; and the user
shall connect again the terminals with that after the test (See
the dielectric voltage test
Type using compression terminals
Ordering positions
9
A
B
C D
E
x x x -
x x -
x x
DC rated voltage, e.g., 1='110 to 250Vdc', selected by the ordering
).
29
30
31
32
33
Short wire
34
35
36
37
38
39
40
FG
Figure 13.5-2 PWS terminal labels
- 1322 -
Chapter Technical description
in
F
G H
J
K
L
-
x x - x x
x
FG
Short wire
Type using ring terminals
6F2S1915 (0.46)
.
Appendix: Notes for
28
27
30
29
31
32
33
34
35
36
38
FG
GRZ200 (Soft 031 & 032)