GOOSE receiving block (GOSUBBLK)
(ii)
This is used for receiving or rejecting GOOSE subscription information from another IED for
testing bad reception. See Chapter
Test flag cancel (S-TestFlagCancel)
(iii)
Test flag in the communication packet will be removed unconditionally, when On is set for
setting [Test flag].
Test for all communication (TestFlag-EN)
(iv)
Setting [TestFlag-EN]=On allows to set test flags at all communication protocol (see Chapter
User interface: Test-submenu
Test for relay application
14.4.2
Auto monitoring function (A.M.F)
(i)
Issuing alarms will be blocked when Off is set for [A.M.F]. For the content about the monitoring
function, see Chapter
Test of cold load protection (CLP-Test)
(ii)
STATE0 or STATE3 will be selected temporally, if STATE0 or STATE3 is set for setting [CLP-
TEST]. See Chapter
ZS, ZG test (ZS-Test.CTRL, ZS-Offset.CTRL, ZS/ZG-Test.XAngle)
(iii)
ZS-Test.CTRL
Setting [ZS-Test.CTRL]=On allows not to operate Zmin feature. For more information about
the Zmin, see Chapter
ZS-Offset.CTRL
Setting [ZS-Offset.CTRL]=Non-Offset allows not to operate offset feature during the test.
ZS-Test.XAngle, ZG-Test.XAngle
Setting [ZS-Test.XAngle]=On allows to take fixed knee characteristic during the test.
Thermal overload function test (THM-Test, THM-IP)
(iv)
Setting [THM-Test]=On allows to have a test value for the pre-load current (Ip). The Ip value
is discussed in Chapter
SOTF test (SOTF-Test)
(v)
Setting [SOTF-Test]=On allows to generate the cold load condition mandatorily for testing,
which is discussed in Chapter
Communication protocol: IEC 61850 communication
).
Automatic supervision function
Relay application: Cold load protection
Relay application: Distance protection
Relay application: Thermal overload function
Relay application: Switch on to fault