logical signal using settings the [OP Mode ID265] etc. For example, the user wishes to record
the output level of the binary output circuit#1 (BO1) at the IO#1 slot, set its PLC monitoring
point '200B01 8002001112' for the setting [OP Mode ID265]; set the displaying name using the
[OP Mode Name265].
Additional triggers for the recording
(iii)
Wishing to start the fault recorder except for the trip instruction, the user can use the PLC
connection points 'ADD_F.RECORD_TRIG1' to 'ADD_F.RECORD_TRIG4', respectively.
Time setting for Pre-fault
(iv)
The instant before the trip is programmable using the setting [Pre-Fault Time] among 10s, 50s,
100s, 200s, 300s.
Unit setting for the quantities
(v)
To change the units of power quantities, go to the metering function discussed in
Metering function
.
- 1009 -
6F2S1915 (0.46)