PSCH class
Attribute Name Attr. Type Explanation
LNName
Data
Common Logical Node Information
OpCntRs
INC
Status Information
ProTx
SPS
ProRx
SPS
Str
ACD_ABC Carrier Send
Op
ACT_ABC Operate
CarRx
ACT
LosOfGrd
SPS
Echo
ACT_ABC Echo signal from weak end infeed function
WeiOp
ACT_ABC Operate signal from weak end infeed function
RvABlk
ACT_ABC Block signal from current reversal function
GrdRx
SPS
Settings
SchTyp
ING
OpDlTmms
ING
CrdTmms
ING
DurTmms
ING
UnBlkMod
ING
SecTmms
ING
WeiMod
ING
WeiTmms
ING
PPVVal
ASG
PhGndVal
ASG
RvAMod
ING
RvATmms
ING
RvRsTmms
ING
Shall be inherited from Logical-Node Class (see IEC 61850-7-2)
LN shall inherit all Mandatory Data from Common Logical Node Class
Resetable operation counter
Teleprotection signal transmitted
Teleprotection signal received
Carrier received after unblock logic
Loss of guard
Guard Received
Scheme Type
Operate Delay Time
Co-ordination timer for blocking scheme
Minimum duration of carrier send signal
Unblock function mode for scheme type
Pickup security timer on loss of carrier guard signal
Mode of weak end infeed function
Co-ordination time for weak end infeed function
Voltage level for weak end infeed function -phase-phase
Voltage level for weak end infeed function -phase-ground
Mode of current reversal function
Pickup time for current reversal logic
Delay time for reset of current reversal output
- 1362 -
6F2S1915 (0.46)
(MICS Ed.1)
T M/O GRZ200
M
O
N
T
M
Y
T
M
Y
M
Y
T
M
Y
O
N
O
N
O
Y
O
Y
O
Y
O
N
O
N
O
N
O
Y
O
N
O
N
O
N
O
N
O
N
O
N
O
N
O
N
O
N
O
Y
GRZ200 (Soft 031 & 032)

Advertisement

loading

This manual is also suitable for:

Grz200