Output signal to monitoring
The SOFTSW1 function shown in Figure 4.3-11, can issue a "Select success" signal at the
output point "S4301_FSD_CSF".
Note: The output point "S4301_FSD_CSF" is the same as the signal shown in Figure
4.3-7.
Select condition
(vii)
Figure 4.3-12 shows the select condition logic of the SOFTSW1 function. The SOFTSW1
function can examine an operate-condition using "Command Blocking" signal
Command blocking*1 defined as "CBK")
Double Command Blocking detected*2
Other devices traveling detected*3
Function "Automatic sequence control" is in progress
ASEQ_MULTI_SEL
Tripping *4 ("General trip")
Control hierarchy (e.g. 43RL) (PLC connection point #3)*6
522001 820A04ED50
S4301_CTRL_RIGHT
IED serious error detected
Figure 4.3-12 Select condition logic for 'ON/OFF' in SOFTSW1
Note: "Command Blocking" disables any operation except its own; see the signal
1
"CBK_STATE (Table 4.3-2)" as the state of "Command Blocking" in the SOFTSW
function.
Note: "Double Command Blocking (DCB_RCV_OR in Table 4.3-8)" is an operation
2
philosophy. It can be used to protect a substation. The user can configure it using
GR-TIEMS.
Note: If the event "device-travelling (Traveling OR in Table 4.3-8)" is detected in the
3
IED, it indicated that another operator is changing the status of a device. Thus,
the IED should inhibit the operation of any device for the duration that the event
is detected.
Note: If tripping (GEN.TRIP in Table 4.3-8) is executed in the IED, any control
4
operation is blocked upon the trip operation. Tripping can be introduced by the
protection function if the IED has protection functions.
SOFTSW1 function (Function ID: 522001)
CBK_STATE
DCB RCV OR
Traveling OR
Unmatched condition detected *5
GEN.TRIP
Command "ON control" received
Command "OFF control" received
S4301_STATE
(522001 000A411001)
Users must setup this condition correctly
SERI_ERR
[S4301-EN]
On
1≥
&
&
received
Same Directional
Controlling Event
- 621 -
6F2S1915 (0.46)
.
1
To selection logic
Select condition
&
&
GRZ200 (Soft 031 & 032)