the new value of "78MW". Note that the compensated value "78MW" is "78,000kW",
and it is not "78,456kW" or "123,456kW". Note that the compensated value will be
affected when there is a change in CT ratio setting. That is, when the user key in a
value of "78MW" for the CT ratio of "2000:1" and later when the CT ratio is changed
from "2000:1" to "4000:1", then the value is displayed as "156MW" on the IED screen.
Therefore when the CT ratio setting is changed, the user should key in the value of
"78MW" again to display the compensated value.
Counter sub-menu: the name and number of statistical items are shown in
two lines. When an item is revised, a [+] mark is shown at the end of the first
line.
Counter
10:48
COUNT1 (No Assign) +
COUNT2 (No Assign) +
COUNT3 (No Assign) +
Figure 12.4-12 Display for Counter sub-menu
To change the counter number, follow the steps as shown in Figure 12.4-13.