Signals from user-PLC logic
ON-control command
(PLC connection point #1)
522001 850A04EDE1
S4301_CHG_TO_ON
Figure 4.3-10 Select logic for ON operation by PLC in SOFTSW1
†Note: Direct operation mode (DIR) is only available.
‡Note: "select condition" signal is provided. See Figure 4.3-12.
Note: To identify the input and output points of the other SOFTSW logics, see Table
††
4.3-3 and Table 4.3-9.
Output signal for monitoring
The SOFTSW1 function shown in Figure 4.3-10, can issue a "Select success" signal at output-
point "S4301_OSD_CSF".
Note: The signal "S4301_OSD_CSF" is the same as the signal shown in Figure 4.3-6.
Receiving "Select command for Off operation" using PLC function
(vi)
Input signal required to connect
Figure 4.3-11 shows the SOFTSW1 logic for a "Select command (PLC-OFF-Control)" signal.
The input signal is generated using the user-programmed PLC logic; the user can connect the
signal for the PLC connection point "S4301_CHG_TO_OFF".
Signals from user-PLC logic
OFF-control command
(PLC connection point #2)
522001 860A04EDE0
S4301_CHG_TO_OFF
Figure 4.3-11 Select logic for OFF operation by PLC in SOFTSW1
†Note: Direct operation mode (DIR) is available only.
‡Note: Signal "select condition" is provided. See Figure 4.3-12.
Note: To identify the input and output points of the other SOFTSW logics, see Table
††
4.3-4 and Table 4.3-9.
510001 7001016D08
Select logic in SOFTSW1
SOFTSW1 function (Function ID: 522001)
For DIR operation†
Operate command
Select condition‡
510001 7001016D08
Selection logic in SOFTSW1
SOFTSW1 function (Function ID: 522001)
For DIR operation†
Operate command
Select condition‡
- 620 -
&
0
&
0
6F2S1915 (0.46)
Output
For monitoring
"S4301_OSD_CSF"
(522001_8F0A411F49)
0
t
Select "success"
0.1s
To "Wait for a command"
t
Select "Failed"
0.6s
††
Output
For monitoring
"S4301_FSD_CSF"
(522001_8D0A411F45)
0
t
Select "success"
0.1s
To "Wait for a command"
t
Select "Failed"
0.6s
††
GRZ200 (Soft 031 & 032)