Setup

WARNING

General

After mechanically attaching the FVP110 to an actuator and finishing the wiring and piping,
connect the FVP110 to a fieldbus and make settings, such as carrying out auto tuning and
setting the tight-shut option, using a parameter setting tool or the like.
For the operation of a parameter setting tool, read the manual of each tool. Also, read
"About Fieldbus" on page 85 through "Actions of the FVP110 During Operation" on
page 109 and "Transducer Block" on page 123 to become familiar with the configuration of
the fieldbus instrument and the function of the transducer block before starting adjustment.
Check that the piping and wiring connections are all correct, and then supply the specified
input voltage and air pressure. For the connection to the fieldbus, see "Wiring and Piping"
on page 51 and "Configuration" on page 89.
Parameter settings for the actuator and valve are made in the FVP110 positioner transducer
block parameters. For details of each parameter, refer to the parameters list in "Function
Block Parameters" on page 183.
Follow the procedure below.
1.
"Set Basic Parameters" on page 60.
2.
"Carrying out Tuning" on page 61.
3.
"Check Valve Actions" on page 63.
4.
"Set Transducer Block Parameters" on page 64.
During the setup, especially when autotuning is being executed, the
valve stem may move suddenly. Before starting the setup, confirm that
the process has been shut down or the control valve is isolated from the
process. During the setup, keep away from the movable parts to avoid
injury.
59
6