GE FVP110 Maintenance Manual page 278

Table of Contents

Advertisement

GE Energy
FVP 110 Fieldbus Valve Positioner Manual
If the difference between the old set point and the new set point is greater than
BOOST_ON_THRESHOLD[2],
BOOST_VALUE[2] functions independently from BOOST_VALUE[1], and the added
value is removed when the deviation enters the range of BOOST_OFF_THRESHOLD[2].
Figure 91 Boost Threshold 1
The boost function of single-acting actuators works only for the air supply side; however,
that of double-acting actuators also works for the exhaust side of OUT1 (for the air
delivery side of OUT2).
If you want to individually set parameters for the exhaust side of OUT1 of double-acting
actuators, set the following parameters.
X_BST_ON_THRESHOLD [1], [2] Tuning range: -10 to 10% (Default: 0, 0%)
X_BST_OFF_THRESHOLD [1], [2] Tuning range: -10 to 10% (Default: 0, 0%)
X_BOOST_VALUE [1], [2] Tuning range: -50 to 50% of MV (Default: 0, 0% of MV)
If you want the boost function of double-acting actuators on the exhaust side of OUT1 to
be asymmetric from the air delivery side, set these parameters. If you set values for these
parameters, input differences for change in relation to the values of
BOOST_ON_THRESHOLD, BOOST_OFF_THRESHOLD, and BOOST_VALUE.
For example, if you want to stop the boost function only on the exhaust side, input a
negative value of the absolute value of BOOST_VALUE[1] in X_BOOST_VALUE[1], and
input the value in X_BOOST_VALUE[2] in the same way to negate the effect. At this time,
you do not need to change the values of X_BST_ON_THRESHOLD and
X_BST_OFF_THRESHOLD.
Theses parameters are valid only for double-acting actuators.
SERVO_I_SLEEP_LMT Tuning range: 0 to 10 sec (Default: 0 sec)
If the deviation changes, the integration operation is stopped for the time of
SERVO_I_SLEEP_LMT to reduce excessive integral components.
If the hysteresis of a valve is large, the valve may not react for a while after an input
change, and a delay in response may occur. This delay in response is accompanied by a
large deviation, and the accumulation of excessive integral components can cause an
overshoot. This parameter is effective in cases such as this.
262

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents