GE FVP110 Maintenance Manual page 209

Table of Contents

Advertisement

Parameters of Transducer Block
Relative
Index
Parameter
Index
54
2054
VALVE_HYS
55
2055
VALVE_SLIP
_WIDTH
56
2056
MEAS_
PRESS_AIR
57
2057
MEAS_
PRESS
_SUPPLY
58
2058
MEAS_
SPRING
_RANGE
59
2059
CONTROL_
DIR
60
2060
THETA_HI(*1)
(*2)
61
2061
THETA_LO
(*1)(*2)
62
2062
THETA_P(*1)
(*2)
63
2063
TRAVEL_
CALIB
_EXEC
64
2064
TRAVEL_
CALIB
_RESULT
65
2065
OPEN_STOP
_ADJ
66
2066
AUTO_TUNE
_EXEC
Table 61 Transducer Block Parameters (Continued)
Default
Name
(factory
setting)
0 %
0 %
0 kPa
0 kPa
0 kPa
2
+ 0.2 rad.
-0.2 rad.
0 rad.
1
1
1
Write
Hysteresis of valve actions (%); a parameter
set by auto tuning
Slip width of valve actions (%); a parameter set
by auto tuning
Air pressure (%); a parameter set by auto
tuning (Valid when an optional pressure sensor
is specified.)
Air supply pressure (%); a parameter set by
auto tuning (Valid when an optional pressure
sensor is specified.)
Spring range of valve; a parameter set by auto
tuning (Valid when an optional pressure sensor
is specified.)
Defines the acting direction of the feedback
loop:
1 = direct
2 = reverse
Upper angle signal limit of position sensor (in
radians)
Upper angle signal limit of position sensor (in
radians)
Angle signal equal to 50 % from position
sensor (in radians)
O/S
Switch for starting a travel calibration.
Indicates the result of a travel calibration.
Not used for FVP110.
O/S
Switch for starting auto tuning.
193
Function Block Parameters
Description

Hide quick links:

Advertisement

Table of Contents
loading