Parameters of Transducer Block
Relative
Index
Parameter
Index
100
2100
SIGN_DATA_
SAVE
101
2101
SIGN_
UPLOAD
_DATABASE
102
2102
SIGN_
UPLOAD
_POINTER
103
2103
SIGN_DATA_
X
104
2104
SIGN_DATA_
Y
105
2105
SIGN_MEAS_
DATE
106
2106
SIGN_
HEADER
_DATA
107
2107
STD_ACT_
SIGN
_SET
108
2108
EXT_ACT_
SIGN
_SET
109
2109
STEP_RESP
_SET
110
2110
POSITIONER
_SIGN_SET
111
2111
SERVO_
WARN
_HI_LIM
112
2112
SERVO_
WARN_
LO_LIM
Table 61 Transducer Block Parameters (Continued)
Default
Name
(factory
setting)
1
1
0
0
0
01/01/00
00:00:00.000
+inf
180, 180, 50
0, 100, 180,
180, 50, 200
45, 55, 100,
600
0, 100, 10, 30,
30
80 % of MV
20 % of MV
Write
Saves the measurements of the standard
actuator signature to non-volatile memory as
record data. 1 = off
Parameter used to specify the measured data
to be uploaded. Set this parameter, and the
related parameters will be read.
Pointer that indicates the leading position of
the data to be uploaded from SIGN_DATA_X or
SIGN_DATA_Y, and used when there are 20 or
more data values measured.
Parameter used to upload the measured
signature data (input data).
Parameter used to upload the measured
signature data (output data).
Parameter used to upload the date and time of
signature measurement
Parameter used to upload the ambient
temperature and settings at signature
measurement
Settings of the standard actuator signature
Settings of the extended actuator signature
and high resolution actuator signature
Settings of step levels for step response test
Settings of the positioner signature
High-limit alarm setting for Servo Output Drift
warning
Low-limit alarm setting for Servo Output Drift
warning
197
Function Block Parameters
Description